The industrial segment SMFVRLA (Valve Regulated Lead Acid) battery for UPS applications is built to perform — in short, the lifeline to your UPS applications. AMARON QUANTA is a product of fail-safe, fool-proof battery technology, produced and tested in our premier manufacturing facility. Built to the highest technical competence in its class, the QUANTA is an example of Amara Raja’s commitment to bringing the best of technology to your table. It features several firsts for the battery industry like the unique Radgrid™.

Description

Specification
Nominal Voltage: 12V
Rated Capacity: 84 Ah / C20 / 1.75VPC / 27°C
Length: 351mm (13.82 in.)
Width: 167mm (6.57 in.)
Total Height: 203mm (7.99 in.)
Approx. Weight: 27.0 Kg (59.52 lbs)
Terminal: M6 x 20mm Bolted

Capacity @ 27°C:
78.2 Ah (10hr, 7.82 A, 10.5 V/battery)
72.0 Ah (5hr, 14.41 A, 10.2 V/battery)
54.5 Ah (1hr, 54.55 A, 9.6 V/battery)

Capacity affected (Temperature at C20 hr rate):
40°C (104°F): 110%
27°C (80.6°F): 100%
0°C (32°F): 80%
-15°C (5°F): 60%

Case Material:
Standard PPCP (12AL084)
FR Version UL 94-V0 (12ALZ084)

Internal Resistance (As per IEC): Approx. 3.54 mΩ (fully charged at 27°C)
Short Circuit Current (As per IEC): 2420 A
Operating Temp. Range: -20°C to +50°C
Nominal Operating Temp. Range: 27°C ± 3°C

Charging (27°C):
Standby use: 13.5 V/battery, Max. charging current 25% of rated capacity, Temp. Compensation ±18mV/battery/°C
Cyclic use: 13.8 V/battery, Max. charging current 25% of rated capacity, Temp. Compensation ±18mV/battery/°C

Self-Discharge: < 4% per month at 27°C

Constant Power Discharge Rating (watts per battery @ 27°C)

ECV/Time 10 min 15 min 20 min 30 min 60 min 2 hrs 3 hrs 5 hrs 8 hrs 10 hrs 20 hrs
1.60 2103 1761 1322 1032 590 381 297.0 193.0 126.0 105.0 52.0
1.65 2085 1721 1309 1000 580 376 285.0 190.0 124.0 104.5 51.5
1.70 2067 1681 1295 967 570 370 273.0 187.0 122.0 104.0 51.0
1.75 2032 1650 1271 951 558 363 271.5 184.0 120.5 103.0 50.5
1.80 1917 1619 1246 934 545 356 270.0 181.0 119.0 102.0 50.0

Constant Current Discharge Rating (amperes @ 27°C)

ECV/Time 10 min 15 min 20 min 30 min 60 min 2 hrs 3 hrs 5 hrs 8 hrs 10 hrs 20 hrs
1.60 189.70 151.62 120.34 91.30 54.55 33.08 22.61 15.56 9.66 8.17 4.50
1.65 183.93 145.12 115.95 87.65 53.86 31.74 21.93 14.99 9.45 8.07 4.39
1.70 178.15 138.61 111.55 84.00 53.16 30.40 21.24 14.41 9.23 7.97 4.27
1.75 171.43 135.48 110.53 83.17 52.50 30.00 21.21 14.36 9.18 7.82 4.20
1.80 168.00 133.33 107.69 82.35 50.24 29.79 21.11 14.24 9.13 7.78 4.18

Notes:

  1. The above data are average values per battery and can be obtained within five charge/discharge cycles.

  2. A tolerance of ±5% applies to the constant power and constant current discharge values.

  3. Recommended to follow IEEE-485 Standard for battery sizing (in terms of aging margin, design margin) for optimal performance and life.

  4. Considerable voltage drop across cables, if any, shall be considered during battery sizing.