Amaron Quanta – 12AL042 12V-42Ah

0 Reviews Write a review
Availability In Stock

The industrial segment SMF battery designed specifically for UPS applications is built to perform — reliably and consistently.

In short, AMARON QUANTA is the lifeline to your critical UPS systems.

Produced and tested in our premier manufacturing facility, AMARON QUANTA is the result of fail-safe, fool-proof battery technology. Built with the highest technical competence in its class, it stands as a testament to Amara Raja’s commitment to delivering the best of technology to you.

The QUANTA features several industry firsts, including the unique Radgrid™ technology, which enhances performance by providing lower internal resistance and superior high-rate discharge capabilities.

Performance

Proven AGM technology that ensures maintenance
free characteristics
A unique heavy duty corrosion-resistant alloy for
positive grids to increase cyclic life in tropical
environments
RadgridTM profile provides lower internal resistance
and superior high-discharge performance
InstachargeTM a patented paste recipe for excellent
charge acceptance
Low self-discharge rates for extended storage periods
Design Float life of upto 10 years
Clean and Sleek looks

Standards

JIS C 8702 Certified
UL (UL-1989) & CE Certified
Complies to IEC 61056, IEC 60896
Complies to IS 16220, IS 15549
Manufactured in ISO 9001, ISO 14001,
OHSAS 18001 certified facilities

Applications

Data Centers
Banks & Financial Markets
Network Operations Centers
Industrial Process Control Facilities
Internet Housing Sites
Semiconductor Manufacturing
Power Generation Plants
Hospital & Testing laboratories

Description

General Specifications

Parameter Value
Nominal Voltage 12V
Rated Capacity 42 Ah / C20 / 1.75 VPC @ 27°C
Dimensions (±2mm)
Length 199 mm (7.83 in.)
Width 167 mm (6.57 in.)
Total Height 175 mm (6.89 in.)
Approx. Weight 14.0 kg (30.86 lbs)
Terminal M6 x 20 mm Bolted
Container Material PPCP (UL 94V-0 optional)

Capacity @ 27°C

Discharge Time Capacity
10 hr (3.91 A, 10.5 V) 39.1 Ah
5 hr (7.20 A, 10.2 V) 36.0 Ah
1 hr (27.2 A, 9.6 V) 27.2 Ah

Effect of Temperature on Capacity (C20 Rate)

Temperature Capacity
40°C (104°F) 110%
27°C (80.6°F) 100%
0°C (32°F) 80%
-15°C (5°F) 60%

Electrical Properties

Parameter Value
Internal Resistance (Fully charged @ 27°C) ~7.6 mΩ
Short Circuit Current 1645 A
Operating Temperature Range -20°C to +50°C
Nominal Operating Temperature 27°C ± 3°C
Self-Discharge (per month @ 27°C) <4%

Charging Parameters @ 27°C

Use Voltage Max Current Temperature Compensation
Standby Use 13.5 V/battery ≤25% of rated capacity ±18 mV/battery/°C
Cyclic Use 13.8 V/battery ≤25% of rated capacity ±18 mV/battery/°C

Constant Power Discharge (Watts per Battery @ 27°C)

ECV / Time 10 min 15 min 20 min 30 min 1 hr 2 hr 3 hr 5 hr 8 hr 10 hr 20 hr
1.60 VPC 1136 882 715 565 330 192 134 91 60 52 25
1.65 VPC 1114 862 704 543 325 189 133 90.5 59.5 51.5 24.5
1.70 VPC 1092 842 693 520 320 185 132 90 59 51 24
1.75 VPC 1051 821 683 513 313 183 131 89.5 58.5 50.5 23.5
1.80 VPC 1010 800 672 505 305 180 130 89 58 50 23

Constant Current Discharge (Amperes @ 27°C)

ECV / Time 10 min 15 min 20 min 30 min 1 hr 2 hr 3 hr 5 hr 8 hr 10 hr 20 hr
1.60 VPC 94.85 75.81 60.17 45.65 27.27 16.54 11.31 7.78 4.83 4.08 2.25
1.65 VPC 91.97 72.56 57.98 43.83 26.93 15.87 10.97 7.49 4.73 4.03 2.20
1.70 VPC 89.08 69.31 55.78 42.00 26.58 15.20 10.62 7.20 4.62 3.98 2.14
1.75 VPC 85.71 67.74 55.26 41.58 26.25 15.00 10.61 7.18 4.59 3.91 2.10
1.80 VPC 84.00 66.67 53.85 41.18 25.12 14.89 10.55 7.12 4.57 3.89 2.09

Note: The above data are typical average values obtainable after a few charge/discharge cycles. A tolerance of ±5% applies. Values may be subject to change as part of ongoing improvements without prior notice.

Reviews

There are no reviews yet.

Be the first to review “Amaron Quanta – 12AL042 12V-42Ah”

Your email address will not be published. Required fields are marked *

Back to Top

Search For Products

Product has been added to your cart
Compare (0)