Description
Battery Specifications – FTA 200 DB
Battery Particulars
| Parameter | Details |
|---|---|
| Battery Type | Maintenance Free Valve Regulated Lead Acid (MF-VRLA) |
| Battery Model | FTA 200 DB |
| Battery Capacity | 200Ah at C10 rate* |
| Volts/Module | 12 Volts |
| Module Dimensions (L x W x H) | (556 x 128 x 322) ± 3mm |
| Module Weight | 59.0 Kgs ± 3% |
Charge Regime
| Parameter | Details |
| Charge Mode | Constant potential mode with current limit |
| Float Charge Voltage | 13.5 volts per module |
| Boost Charge Voltage | 13.8 volts per module |
| Current Limit (CL) | Max. 30% of the rated capacity |
| Recommended Voltage Compensation | For every 1°C rise, reduce float voltage by 0.003VPC & vice versa. Ensure extension of temperature sensor up to the battery. |
Product Details
| Parameter | Details |
| AH Efficiency | Above 95% |
| WH Efficiency | Above 85% |
| Self-Discharge/Month | <4% of rated capacity |
| Operating Temperature | -20°C to +60°C (peak for short durations) |
| Recommended Max Storage | 6 months from dispatch date, store in a covered area |
| Container Material | FR-PPCP |
| Type of Separator | Highly absorbent Micro porous spun glass matrix (AGM) |
| Terminal | M8 Top terminal |
| Design Float Life | 12+ years |
Applicable Standards
| Standards | Details |
| Conforms to | IEC 60896-21 & 22: 2004 Standards |
Note: Batteries may initially deliver 90–95% of rated capacity upon delivery. Full 100% capacity is achieved after a few charge/discharge cycles as per IEEE-485 clause no: 6.2.4 STD.